SPECIFICATIONS FOR NORMAL
WEIGHT
CONCRETE MASONARY UNITS
Normal Weight Concrete Masonary Units: Units shall be equal to
JNW weries, as manufactured by A. Jandris & Sons, Inc., Gardner, MA or an
approved substitute. Units shall comply with all requirements of the current
issue of the following standards and with other requriements specified herein.
- Hollow & Solid Loadbearing Units: Shall compy with all provisions
as ASTM C90-96a, Type I, Class I, Moisture Controlled Units.
- Compressive Strenghts: All units shall have a minimum compressive
strenght on the net area of 1900 PSI when tested in accordance with ASTM C-140.
- Normal Weight Concrete Masonary Units: Sahll be composed of normal
weight siliceous aggregates conforming to ASTM C-33.
- All Concrete masonary units (architectual, Standard & Backups) for this
project shall be produced by one manufacturer.
- Bidders who desire to use other manufacturers shall submit samples and technical
data to the architect for evaluation, inspection, and written approval prior
to the bid date covering this section. If the products are approved, an addenda
will be issued.
- Optional - Choose as Appropriate
- Expect as noted on the drawings, all unit faces exposed to view shall
be scored as herein describes. Unit faces hidden from view need not be
simarlarly scored, but may be unless sotherwise noted on the drawings.
- Units shall have one vertical square edge score 3/8" x 3/8"
located in the center of the exposed face.
- Where a fire resistance rating is shown on the drawings, provide units
meeting that requirement when rated in accordance withe Equivalent Thickness
Method of the Building Officials Conference of America, Inc.
- Insulation: insters shall be installed in the cores of the blocks at
teh block producer's plant, Korfil "U" shaped units or Icon
Single face units as manufactured by the Concrete Block Insulating Systems,
West Brookfield, MA. Inserts shall be properly installed to allow blocks
to handled without danger of insert dislodgment.
- Units shall be manufactured with an intergal water repellant system
(such as "Dry Block"). Units shall be manufactured by a qualified
producer.
NOTE TO SPECIFIER: This information may be used as a complete material
section. It should be supplemented by an appropriate workmanship specification.